Bus cables |
|
Product Name/Code :
Profibus L2 Torsion + Festoon |
|
Construction:
Type/Area of Application |
Torsion Applications |
Mobile Use |
Cable Construction |
1x2x0.64 mm (stranded) |
1x2x0.65 mm (stranded) |
Inner Conductor Diameter 1 |
Copper, bare (AWG 23/19) |
Copper, bare (AWG 24/19) |
Conductor Insulation |
Foam-skin-PE |
Cell PE |
Conductor Colors |
red, green |
red, green |
Stranding Element |
2 conductors + 2 fillers stranded together |
2 conductors + 2 fillers stranded together |
Shielding 1 |
Polyester foil over stranded bundle |
Polyester foil over stranded bundle |
Shielding 2 |
Polyester foil, Copper bare |
Polyester foil, aluminum-lined |
Total Shielding |
Copper shifting, tinned |
Copper braid, tinned |
Outer Jacket Material |
PUR |
PVC |
Outer Diameter |
8.0 mm ± 0.3 mm |
8.0 mm ± 0.3 mm |
Outer Jacket Color |
Violet |
Green |
Electrical Data:
CharacteristicImpedance@3-20Hz |
150 Ω ± 10 Ω |
Conductor Resistance |
66.5 Ohm/km max. |
Insulation Resistance |
1.00 GOhm x km min. |
Mutual Capacitance@1KHz |
30.0 nF/km nom. |
Working Voltage |
Max: 250 V |
Test Voltage |
1.5 KV |
Attenuation: |
9.6 |
kHz |
< |
3.0 |
dB/km |
38.4 |
kHz |
< |
5.0 |
dB/km |
4.0 |
MHz |
< |
25.0 |
dB/km |
16.0 |
MHz |
< |
51.0 |
dB/km |
Technical Data:
Weight |
approximately 91.0 kg/km |
approximately 64.0 kg/km |
Min. Bending Radius (Laying) |
12.5 x OD mm |
5 x OD mm |
Operating Temp.Range, min. |
- 5 °C |
-40 °C |
Operating Temp.Range, max. |
+60 °C |
+60 °C |
|
|
|
|
|
|
|
|
|
|