NSGAFOU Cables
Application
The cables are designed for use in switch cabinets, wiring of devices, trains and buses as well as in dry rooms.
Standards
● DIN VDE 0250-602
Construction
Conductors
Flexible tinned copper to IEC 60228 class 5.
Insulation
EPR type 3G13.
Outer sheath
PCP type 5GM3.
Electrical Characteristics at 20℃
Nominal Conductor Cross Section |
mm² |
1.5 |
2.5 |
4.0 |
6.0 |
10 |
16 |
25 |
35 |
Conductor Resistance |
Ω/km |
13.7 |
8.21 |
5.09 |
3.39 |
1.95 |
1.24 |
0.795 |
0.565 |
Current Rating |
A |
31 |
41 |
58 |
75 |
103 |
145 |
194 |
240 |
Voltage Rating |
KV |
1.8/3 |
Nominal Conductor Cross Section |
mm² |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
Conductor Resistance |
Ω/km |
0.393 |
0.277 |
0.21 |
0.164 |
0.132 |
0.109 |
0.0817 |
Current Rating |
A |
301 |
372 |
456 |
528 |
607 |
639 |
821 |
Voltage Rating |
KV |
1.8/3 |
Mechanical and Thermal Properties
Minimum Bending Radius: 4×OD
Temperature Range:-25℃ to +80℃ (during operation); -10℃ to +60℃ (during installation) |