Construction 
                                      Bare copper, extra fine wire conductor to DIN VDE 0295 cl. 6 and IEC 60228 cl. 6; 
                                      Oil-resistant special PVC insulation; 
                                      Color see table, or as desired;  
                                      If this cable is to be double-insulated, then its external diameter and weight must be adapted;  
                                      Caution with existing cables. 
                                       
                                      Properties  
                                      PVC self-extinguishing and flame retardant, test method B according to VDE 0472 part 804 and IEC 60332-1;  
                                      Chemical resistance see table Technical Information.  
                                      Temperature range: flexing -5°C to +80°C; fixed installation -40°C to +80°C  
                                      Nominal voltage: U0/U 600/1000 V  
                                      A.C. test voltage, 50 Hz: 3000 V  
                                      Minimum bending radius: for flexible installation; approx. 7,5 cable Ø                                       
                                       |