Standards
• EN 50200:2000-02
• EN 50266
• EN 50267
• EN 50268
• BS 6387
• IEC 60331
• DIN VDE 0472-814
Construction
Conductors
Solid annealed bare or tinned copper sized 0.6/0.8/0.9mm as per class 1 of VDE 0295/IEC 60228
Insulation
Silicon Rubber compound as per DIN VDE 0266
Twisted Pairs
Insulated conductors are twisted into pairs with varying lay length to minimize crosstalk
Cabling Element
Twisted Pairs
Core Assembly
The twisted pairs are stranded to the core in layers
Core Wrapping
One or more non hygroscopic polyester tapes are helically or longitudinally laid with an overlap prior to sheathing
Screen
A laminated Aluminium/Polyester tape is placed in contact with solid copper 0.6mm or 0.8mm drain wire
Inner bedding (for armoured cables)
PE or LSZH compound.
Armour (for armoured cables)
Either corrugated steel tape armour or galvanized steel wire is applied over an inner polyethylene sheath. For steel tape armour, the 0.15mm thick steel tape is coated with a copolymer and applied with an overlap. For steel wire armour, single layer of galvanized steel wire armour is applied
Sheath
LSZH compound HM2 as per VDE 0207-24
Ripcord
Nylon ripcord may be placed parallel to the cores to facilitate sheath removal
Drain Wire
A solid tinned earth/continuity wire shall be laid longitudinally for screened cables
|