450/750V LSZH Insulated, Non-sheathed Power Cables (single core)
STANDARDS
Basic design to BS 7211
FIRE PERFORMANCE
Flame Retardance (Single Vertical
Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE
0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation
(Vertically-mounted bundled wires
& cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
450/750V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: LSZH compound
CONSTRUCTION PARAMETERS
Conductor |
FTX100 07Z1-R |
No. of Core X
Cross Section |
No./Nominal
Diameter of
Strands |
Nominal
Insulation
Thickness |
Nominal
Overall
Diameter |
Approx. Weight |
Noxmm2 |
No./mm |
mm |
mm |
kg/km |
1x1.5 |
7/0.53 |
0.7 |
3.1 |
23 |
1x2.5 |
7/0.67 |
0.8 |
3.7 |
35 |
1x4 |
7/0.85 |
0.8 |
4.3 |
52 |
1x6 |
7/1.04 |
0.8 |
4.8 |
73 |
1x10 |
7/1.35 |
1.0 |
6.2 |
120 |
1x16 |
7/1.70 |
1.0 |
7.2 |
180 |
1x25 |
7/2.24 |
1.2 |
9.0 |
285 |
1x35 |
19/1.53 |
1.2 |
10.2 |
375 |
1x50 |
19/1.78 |
1.4 |
12.0 |
510 |
1x70 |
19/2.14 |
1.4 |
14.0 |
720 |
1x95 |
19/2.52 |
1.6 |
16.0 |
995 |
1x120 |
37/2.03 |
1.6 |
18.0 |
1230 |
1x150 |
37/2.25 |
1.8 |
20.0 |
1520 |
1x185 |
37/2.52 |
2.0 |
22.0 |
1900 |
1x240 |
61/2.25 |
2.2 |
25.0 |
2480 |
1x300 |
61/2.52 |
2.4 |
28.0 |
3100 |
1x400 |
61.2.85 |
2.6 |
31.5 |
3950 |
1x500 |
61/3.20 |
2.8 |
35.0 |
4950 |
1x630 |
127/2.52 |
2.8 |
39.0 |
6360 |
|